Operation
On
initial start up the steam system, large amounts of cold condensate
and air are present in the system. At this point the bimetallic
strip of the delta element relaxes and fully opens the valve assembly
to quickly expel the high volume of non-condensate gases and cold
condensate through the discharge port.
As the element senses an increase in the condensate temperature
the bimetal expands and raises the stem to modulate the flow.
Just below the temperature of saturated steam the seat will close
tightly to prevent live steam from discharging.
Application
Bestobell model DM25 is a light performance,energy efficient steam
trap that incorporates a 'Y' type strainer and integral check
valve. It provides long term reliable service on steam main dripleg
and critical tracing applications with differential pressures
up to 320 PSI.